Updated November 2026
An off grid solar system SLD, or single line diagram, is a one-page drawing that shows every major component in your system and how they connect. Once you finish this guide, you will know which symbols to use, what order to place them in, and which values to label so an installer or inspector can follow your design. The diagram also doubles as a planning tool, because it forces you to check that your panel, controller, battery and inverter ratings actually agree with each other.
Gather the Ratings Before You Draw
A single line diagram is only as useful as the numbers printed on it. Pull the nameplate or spec sheet for each component first, then write the values down before you touch any software.
Shopping for one? See our guide: 6 Best DIY Solar Power System Kit Options for Off-Grid Homes (2026).
- Panel array: total wattage, open-circuit voltage (Voc), short-circuit current (Isc), and how many strings you plan to run.
- Charge controller: maximum PV input voltage, maximum charge current, and battery voltage setting (12 V, 24 V or 48 V).
- Battery bank: nominal voltage, amp-hour capacity, and chemistry (lead-acid or lithium).
- Inverter: continuous and surge output ratings, DC input voltage range, and whether it has a built-in transfer switch.
- Overcurrent protection: fuse or breaker ratings for each conductor run.
Lay Out the Components in Signal Order
Standard practice is to draw the system left to right or top to bottom in the order power flows: array, then combiner or disconnect, then charge controller, then battery bank, then inverter, then the AC panel and loads. Use the standard symbols for PV modules, fuses, disconnects, batteries and inverters so anyone reviewing the drawing reads it at a glance.
Keep the DC side and AC side visually separate. Draw a clear boundary, label DC conductors with voltage and wire gauge, and mark AC conductors with voltage, phase and breaker size. Many reviewers also expect a grounding symbol and a note on where the equipment grounding conductor bonds to the system.
Label Every Conductor Run
Each line between components should carry three labels: the conductor size (for example, 10 AWG PV wire), the run length if it matters for voltage drop, and the protective device at the source end. A conductor with no label is the most common reason a diagram gets sent back for revision. Types of Home Solar Systems: Grid-Tied, Hybrid, Off-Grid goes further into this.
Check the Diagram Against Your Ratings
Before you finalize the drawing, verify that the numbers chain together correctly. Array voltage at the coldest expected temperature must stay under the controller’s maximum input. Battery voltage must match the controller and inverter settings. The inverter’s continuous rating must exceed your largest expected simultaneous AC load, and the DC cable and fuse must handle the current the inverter draws at full output.
| Check | What to Confirm |
|---|---|
| Array voltage | Cold-temperature Voc of series strings stays below controller maximum |
| Battery voltage | Matches controller setting and inverter DC input |
| Charge current | Array output does not exceed controller charge limit |
| Inverter sizing | Continuous rating covers peak simultaneous AC load |
| Protection | Every conductor has a fuse or breaker sized to its ampacity |
If you are still choosing components, the Wiring Diagram for Off-Grid Solar System: A Step-by-Step Guide walks through the same connections in a more visual format. For sizing the battery bank that feeds your inverter, see Planning an Off-Grid Solar System: 8 Steps to Size It Right.
Common Mistakes
- Drawing the array as one block when it is really several series strings, which hides a voltage problem.
- Forgetting the DC disconnect between the battery and inverter.
- Using lead-acid battery values on a lithium system, or the reverse.
- Omitting the grounding and bonding path entirely.
- Leaving wire gauges and fuse ratings off the drawing, so the reviewer has to guess.
Recommended Gear
A drafting tool with a library of standard electrical symbols saves time and keeps your drawing consistent with what inspectors expect.
- A dedicated electrical schematic drawing program with solar symbol libraries makes it easy to keep labels aligned and reusable. View on Amazon
- A clipboard-sized printed symbol template helps when sketching by hand before moving to software. View on Amazon
FAQ
Do I need a stamped single line diagram for a home off grid system?
Requirements depend on your local jurisdiction and the permit you are pulling. Many areas ask for a diagram with the permit application, so check with your building department and consult a licensed electrician or engineer for the final version.
What software works best for drawing an SLD?
Any program that supports standard electrical symbols and lets you add text labels will work. Choose one you can export to PDF, since that is the format most reviewers request.
How detailed should the labels be?
Include conductor size, voltage, protective device rating and component model or rating on every major element. If a value is missing, the reviewer will usually ask for it before approving the design.
Conclusion
A clear single line diagram turns a pile of components into a system you can check, build and explain. Start with accurate ratings, lay out the power flow in order, and verify that voltages and currents match at every connection. Confirm local permit requirements before you finalize the drawing.